| MA005X |
Universal
Isolated Analog Interface Module
|
|
Features:
- Three port isolation module
with voltage, current and JK thermocouple inputs
- High accuracy and stability
over operating temperature range
- Current and voltage outputs
provided
- Voltage output buffered with
short circuit protection
- Visual indication of open
thermocouple or current loop
- Selectable jumpers for many
isolated conversion OPTIONS
- 120VAC or 230VAC input power
supply
- Panel mount or universal DIN
rail mount
|
|
|
Description:
The MA005X is a compact multipurpose
member of the intelliBLOCK® family. It is a self-contained
subsystem providing a true three port isolation function. The
inputs can range from voltages (uni or bi-directional), currents
and J or K thermocouples. The output is galvanically isolated
from the input utilizing transformer coupling. The output is
presented as a current and voltage and can be used as simultaneously
in most instances. The voltage output is buffered allowing it
to drive signal cables over long distances. This allows the MA005X
to be situated in the vicinity of the sensor and provide enough
signal drive for remotely mounted data acquisition systems. The
current output has a visual indication of open loop and compliance
problems. The thermocouple input has visual indication of open
loop conditions. There is a bandwidth selection jumper enabling
30Hz or 2KHz operation. The 30Hz option is recommended for slow
changing noisy signals. The 2KHz option is recommended for isolating
signals that require more bandwidth such as motor control applications.
These features make the MA005X a truly universal isolation analog
interface. The MA005X is an intelligent choice for accurately
isolating and converting signals for data acquisition systems
and programmable logic controllers.
|
|
Specifications:
|
Supply voltage : |
120VAC,
230VAC |
| Supply current : |
40ma.,
20ma. |
| Operating temp : |
0 to 70 degrees celcius
0 to 50 degrees celcius for thermocouple input
|
| Fuse : |
MDL
250V @ 1/8A. (all models) |
| Inputs : |
VOLTAGE - +/- 10VDC max.
CURRENT - 0-50ma. max.
THERMOCOUPLE - J or K, 480 degrees (C)
or 896 degrees (F) max.
|
| Outputs : |
VOLTAGE - +/- 10 VDC @ 150ma. short circuit protected
10mV/degrees celcius for thermocouple input
CURRENT - 0 - 20ma. range
|
| CMV isolation : |
+/- 1000V peak continuous
|
| Nonlinearity : |
+/-
0.05% max. |
| Accuracy : |
THERMOCOUPLE - Stability vs. temp at +/- 0.05 degrees
celcius/degrees celcius max. Gain error at +/- 0.75%
max.
CURRENT - 0.1% overall
|
| Dimensions : |
104mm
x 104mm x 70mm (L x W x H) |
| Mounting : |
Panel
or Universal DIN rail mount |
| (Temperature
@ 25 degrees celcius) |
|
|